momo0720
人外有人,天外有天!
級別: 工控俠客
|
現場機臺跳這個異常 查好像是BUS通訊異常 一天大概會發生三次 復機後重開又好了..... 請問這是硬體的關係還是軟體有關係呢? |
|
---|---|---|
|
wwcwwc
級別: VIP會員
|
如果光看你的問題標題,只能是軟件編程問題。可能你使用了非法語句。 可以在線監控cpu的報警信息。 |
---|---|
|
momo0720
人外有人,天外有天!
級別: 工控俠客
|
感謝 你的回覆 這個機器已經使用很久 最近才發生這樣的問題 如果使用非法語句 那應該是一開始就會發生. 是嗎? |
|
---|---|---|
|
sjm213
有小知識,無大學問。
級別: 論壇版主
|
SF紅燈是系統故障system fault; BUSF紅燈時網絡故障,它也可能引起SF亮。 所以優先檢查網絡,尤其是網絡接頭。在紅燈亮起時在線監控網絡通訊情況,通訊不上的子站會有一個紅色斜桿標識,檢查或更換有紅杠的第一個子站接頭。 |
---|---|
|
guochunyi
直讀解西門屏HMI口令 。。。
級別: 論壇版主
|
在線查看故障信息記錄也可以得到幫助,能分析是什么地方出現的問題。 |
|
---|---|---|
|
momo0720
人外有人,天外有天!
級別: 工控俠客
|
各位師傅 我在PLC的訊息裡面得到以下消息 像這樣我怎麼知道要去哪裡做異常判斷呢? 做怎樣的處理? Diagnostic buffer of module CPU 315-2 DP Order No./ Description Component Version 6ES7 315-2AF03-0AB0 Hardware 1 - - - Firmware V 1.2.0 Rack: 0 Slot: 2 Event 1 of 10: Event ID 16# 4302 Mode transition from STARTUP to RUN Startup information: - Time for time stamp at the last backed up power on - Single processor operation Current/last startup type: - Automatic warm restart after backed up power on Permissibility of certain startup types: - Manual warm restart permitted - Automatic warm restart permitted Last valid operation or setting of automatic startup type at power on: - Automatic warm restart after backed up power on Previous operating mode: STARTUP (warm restart) Requested operating mode: RUN Incoming event 09:16:13.960 AM 09/26/2013 Event 2 of 10: Event ID 16# 1382 Request for automatic warm restart STOP due to: STOP caused by stop switch being activated Startup information: - Startup without modified system configuration - No difference between setpoint and actual configuration - Time for time stamp at the last backed up power on - Single processor operation Current/last startup type: - Automatic warm restart after backed up power on Permissibility of certain startup types: - Manual warm restart permitted - Automatic warm restart permitted Last valid operation or setting of the automatic startup type at power on: - Automatic warm restart after backed up power on Requested OB: Startup OB (OB100) Priority class: 27 Incoming event 09:16:13.956 AM 09/26/2013 Event 3 of 10: Event ID 16# 4301 Mode transition from STOP to STARTUP STOP due to: STOP caused by stop switch being activated Startup information: - Time for time stamp at the last backed up power on - Single processor operation Current/last startup type: - Automatic warm restart after backed up power on Permissibility of certain startup types: - Manual warm restart permitted - Automatic warm restart permitted Last valid operation or setting of the automatic startup type at power on: - Automatic warm restart after backed up power on Previous operating mode: STOP (internal) Requested operating mode: STARTUP (warm restart) Incoming event 09:16:13.712 AM 09/26/2013 Event 4 of 10: Event ID 16# 5371 Distributed I/Os: End of the synchronization with a DP master/IO controller on slot 2 Number of distributed stations: 6 Incoming event 09:16:13.235 AM 09/26/2013 Event 5 of 10: Event ID 16# 4300 Power on backed up Previous operating mode: No voltage Requested operating mode: STOP (own initialization) Incoming event 09:16:07.211 AM 09/26/2013 Event 6 of 10: Event ID 16# 494E Power failure Previous operating mode: STOP (internal) Requested operating mode: No voltage External error, Incoming event 09:08:37.623 AM 09/26/2013 Event 7 of 10: Event ID 16# 4303 STOP caused by stop switch being activated Previous operating mode: RUN Requested operating mode: STOP (internal) Incoming event 09:08:09.773 AM 09/26/2013 Event 8 of 10: Event ID 16# 38C4 Distributed I/Os: station return Address of the affected DP slave: station number: 20 DP master system ID: 1 Log. base address of the DP slave: Input address: 1017 Log. base address of the DP master: 1023 Requested OB: Rack failure OB (OB86) Priority class: 26 External error, Outgoing event 08:57:55.883 AM 09/26/2013 Event 9 of 10: Event ID 16# 2942 I/O access error, reading P area, word access, Access address: 90 Requested OB: I/O access error OB (OB122) Priority class: 1 External error, Incoming event 08:57:55.826 AM 09/26/2013 Event 10 of 10: Event ID 16# 2942 I/O access error, reading P area, word access, Access address: 90 Requested OB: I/O access error OB (OB122) Priority class: 1 External error, Incoming event 08:57:55.803 AM 09/26/2013 |
|
---|---|---|
|